| Boiler
Accessories
Boiler
Sensor SR2

The
SR2 is used for monitory conductivity in a boiler blowdown line. The
SR2 cannot be used after a sample cooler.
-
Body
Carbon Steel
-
Electrodes
416SS
-
Insulator
Peek
-
Max
Pressure 600 psi (41.4 bar)
-
Max
Temperature 460° F (238°C)
-
Cable
20 ft High temp
-
Process
thread ¾ inch MNPT
-
Conduit
connection ¾ inch MNPT
Boiler
Sensor SR4

The
SR4 can be in the boiler blowdown line or with a sample cooler. The
SR4 can only be used with the 2250 and 2255.
-
Body
316SS
-
Electrodes
Titanium
-
Insulator
Peek
-
Max
Pressure 250 psi (17.2 bar)
-
Max
Temperature 392° F (200°C)
-
Cable
20 ft High temp
-
Process
thread ¾ inch MNPT
-
Conduit
connection ¾ inch FNPT
-
Temperature
comp 4K NTC
MBV1
and MBV2

|
MBV1 |
MBV2 |
|
Size
½
inch
NPT |
Size
¾
inch
NPT |
|
Body
Carbon Steel |
Body
Carbon Steel |
|
Rating
250 psi @ 400°
F
(17.2 bar @ 204°C) |
Rating
250 psi @ 400°
F
(17.2 bar @ 204°C) |
|
Seals
Reinforced TFE |
Seals
Reinforced TFE |
|
Ball
316SS |
Ball
316SS |

PL5

The
PL5 is used as a sample/cycle method in boilers. The orifice
restricts flow near the boiler sensor to prevent steam flashing
during a sample. The PL6 can also be used as a PL5.
PL6

The
PL6 is used for a continuous sampling of a boiler. The lower orifice
bleeds a small sample across the sensor. The upper orifice is used
with the motorized ball valve and opens when the conductivity is
above set point. |